DGBS 450 ST
Industrial range three-phase, soundproof generator, operating in automatic mode, manual mode, signal mode, or test mode. A commitment to quality energy.
Power (PRP / ESP):
402 / 443 kVA (322 / 354 kW)
VERSION:
Soundproofed
VOLTAGE:
400/230V
EMISSIONS LEVEL: EU Stage 0
CE DECLARATION OF CONFORMITY
Another version of this product
DGBS 450 ST
DGBS 450 ST
DGBS 450 ST
DGBS 450 ST
DGBS 450 ST
DGBS 450 ST
PRODUCT DETAILS
VERSION
Soundproofed
Fuel
Diesel
Voltage
400/230V
RPM
1500
Number of phases
3
L (mm)
4600
W (mm)
1606
H (mm)
2236
Weight (Kg)
4200
Engine make and model
BAUDOUIN 6M21G440/5
Type of regulation
Electronic
Refrigeration
Water-cooled
Emissions
EU Stage 0
Consumption 50%
43,2 l/h
Consumption 75%
63,5 l/h
Consumption 100% PRP
85,5 l/h
Consumption 100% ESP
94,8 l/h
Tank size (l)
840 l
Autonomy 50% PRP
19,4 h
Autonomy 75% PRP
13,2 h
Autonomy 100% PRP
9,8 h
Autonomy 100% ESP
8,9 h
Alternator make and model
STAMFORD S4L1D-F
Type of alternator regulation
AS440
Switch model
Schneider EasyPact 630A 4P
Amps ESP (A)
639,4
Make and model
DSE 7320 MKII
DGBS 450 ST
Range Industrial
| 50Hz
Do you need an ATS for your installation?
CONTACTORS TRANSFER SWITCHES
Switching panels between mains and genset with Schneider Electric contactors and enclosure from the same manufacturer. With mechanical and electrical interlocking and switching management from the control panel. They have an optional mains failure detector.
REMOTELY OPERATED MOTORISED TRANSFER SWITCH (RTS)
Transfer switches with remote-operated 4-pole fully visible break. They allow in-load transfer of two three-phase sources via remote-voltage-free contacts, from an external automatic controller, using pulse logic or a switch.
They are designed for use in low-voltage power systems where a brief interruption of load power during transfer is acceptable.
Interested in learning more about this generator? Simply fill out the form below to receive all the details
* Remember to fill out all required fields