DGIS 220 ST
Industrial range three-phase, soundproof generator, operating in automatic mode, manual mode, signal mode, or test mode. A commitment to quality energy.
Power (PRP / ESP):
200 / 220 kVA (160 / 176 kW)
VERSION:
Soundproofed
VOLTAGE:
400/230V
EMISSIONS LEVEL: EU Stage 0
CE DECLARATION OF CONFORMITY
Another version of this product
DGIS 220 ST
DGIS 220 ST
DGIS 220 ST
DGIS 220 ST
DGIS 220 ST
DGIS 220 ST
PRODUCT DETAILS
VERSION
Soundproofed
Fuel
Diesel
Voltage
400/230V
RPM
1500
Number of phases
3
L (mm)
3412
W (mm)
1162
H (mm)
1840
Weight (Kg)
2400
Engine make and model
IVECO N67 TM7
Type of regulation
Mechanical
Refrigeration
Water-cooled
Emissions
EU Stage 0
Consumption 50%
24 l/h
Consumption 75%
37,3 l/h
Consumption 100% PRP
42,1 l/h
Consumption 100% ESP
49 l/h
Tank size (l)
425 l
Autonomy 50% PRP
17,7 h
Autonomy 75% PRP
11,4 h
Autonomy 100% PRP
10,1 h
Autonomy 100% ESP
8,7 h
Alternator make and model
STAMFORD UCI274H
Type of alternator regulation
AS440
Switch model
Schneider EasyPact 400A 4P
Amps ESP (A)
317,5
Make and model
DSE 6020 MKII
DGIS 220 ST
Range Industrial
| 50Hz
Do you need an ATS for your installation?
CONTACTORS TRANSFER SWITCHES
Switching panels between mains and genset with Schneider Electric contactors and enclosure from the same manufacturer. With mechanical and electrical interlocking and switching management from the control panel. They have an optional mains failure detector.
REMOTELY OPERATED MOTORISED TRANSFER SWITCH (RTS)
Transfer switches with remote-operated 4-pole fully visible break. They allow in-load transfer of two three-phase sources via remote-voltage-free contacts, from an external automatic controller, using pulse logic or a switch.
They are designed for use in low-voltage power systems where a brief interruption of load power during transfer is acceptable.
Interested in learning more about this generator? Simply fill out the form below to receive all the details
* Remember to fill out all required fields