Share:

BGVW 400 ST

Balance range three-phase open generator, operating in automatic mode, manual mode, signal mode, or test mode. The most balanced energy for emergency applications.

Power (PRP / ESP):

455 / 500 kVA (364 / 400 kW)

VERSION:

Open

VOLTAGE:

208/120V

EMISSIONS LEVEL: EU Stage II

CE DECLARATION OF CONFORMITY

BGVW 400 ST

BGVW 400 ST

BGVW 400 ST

BGVW 400 ST

BGVW 400 ST

BGVW 400 ST

PRODUCT DETAILS

  • General information

    VERSION

    Open

    Fuel

    Diesel

    Voltage

    208/120V

    Rpm

    1800

    Phase

    3

  • Size and weight

    Version

    Open

    L (mm)

    3400

    W (mm)

    1550

    H (mm)

    2233

    Weight (Kg)

    4000

  • Engine

    Type of regulation

    Electronic

    Refrigeration

    Water-cooled

    Emissions

    EU Stage II

    Consumption 75%

    70 l/h

    Consumption 100%

    103,6 l/h

  • Tank and autonomy

    Tank size (l)

    820 l

    Autonomy 50% PRP

    17,1 h

    Autonomy 75% PRP

    11,7 h

    Autonomy 100% PRP

    8,7 h

    Autonomy 100% ESP

    7,9 h

  • Alternator

    Alternator model

    STAMFORD S4L1D-F

    Type of alternator regulation

    AS440

  • Switch

    Switch model

    Chint 1600A 4P

    Amps ESP (A)

    1387,9

  • Control unit

    Switchboard model

    1387,9

  • BGVW 400 ST

    BGVW 400 ST

    Spectrum

    | 60Hz

    Do you need a switchboard for your installation?

    SWITCHES BY CONTACTS

    Dagartech contactores

    Switching panels between mains and genset with Schneider Electric contactors and enclosure from the same manufacturer. With mechanical and electrical interlocking and switching management from the control panel. They have an optional mains failure detector.

    MOTORISED SWITCHES

    Dagartech contactores

    Fully apparent cutoff 4-pole remote operated transfer switches. They permit the on-load transfer of two three-phase sources via de-energised remote contacts from an external automatic controller using pulse logic or a switch.

    They are designed for use on low voltage power systems where a brief interruption of power to the load during transfer is acceptable.